Home > Capacitor, Fuse, Circuit Breaker > FSC 5925 > 5925-00-919-8075

5925-00-919-8075, 5925009198075 NSN Information

Request for Quote

Manufacturer Part Number(s):AM3333MG6-7-5-250-400-16, AM4C3A7-5-3, C1034-7

FSC NIIN ITEM NAME
5925 009198075 CIRCUIT BREAKER
INC ESDC HMIC
0013 P

5925-00-919-8075 MCRD (Master Cross Reference Data)

Mfg. Part # Mfg. Name CAGE RNCC RNVC ISC MSDS SADC DAC HCC
AM3333MG6-7-5-250-400-16 EATON CORP 74193 5 9 2
AM4C3A7-5-3 EATON CORP 74193 3 9 2
C1034-7 LOCKHEED MARTIN CORPORATION 81755 7 2 2

5925-00-919-8075 Characteristics

MRC Requirement Statement Characteristics
CPRJ TRIP RELEASE METHOD MAGNETIC ALL LOCATIONS
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
AXHR MOUNTING FACILITY TYPE AND QUANTITY 8 THREADED HOLE
CPRW ACTUATOR FUNCTION RESET
ADAQ BODY LENGTH 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
APNQ III ARC QUENCHING METHOD MAGNETIC BLOWOUT
TTQY TERMINAL TYPE AND QUANTITY 8 THREADED STUD
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 AC ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
CPRQ RESET METHOD MANUAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, THREE, AND FOUR LINKED
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 7.5 AMPERES AC ALL LOCATIONS
AFJN III FRAGILITY FACTOR MODERATELY RUGGED
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
THSD THREAD SERIES DESIGNATOR UNC
ADTV CASE MATERIAL PLASTIC
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AJEC BOSS HEIGHT 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.170 MINIMUM AT 200 PCT AND 1.700 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 4 TOGGLE
CMLP THREAD QUANTITY PER INCH 32
BBRG III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CQJX NOMINAL THREAD SIZE 0.138 INCHES
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM
ADAT BODY WIDTH 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
AKPX POLE QUANTITY 4
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE